SVR is KEMA type tested and designed for use on overhead distribution lines as well as distribution substation applications for all voltage levels up to 15.5kV,27kV and 38kV.
Download:
Features
Reliability
10,000 times mechanical endurance
UV resistant solid insulation material
100% Factory Acceptance Testing
Single molded design ensure longer creepage distance
Maintenance-free
Solid insulation material enables application under high contamination environment
Magnetic Actuator with few moving parts
Painted Stainless steel enclosure and operation shaft guarantee maximum corrosion protection
Environmentally Friendly
SF6 free
Altitude: 3000m
Operating temperature: -40 to 55°C
Maximum solar radiation: 1.1 kW/m2
Icing thickness: 20mm
Pollution level: IV-Very Heavy
Seismic intensity: ≤8
Wind pressure: ≤34 m/s
Humidity: Daily Average ≤95%; Monthly Average≤90%
Flexibility and Compatibility
Compatible with controller or relays from other brands
Various selections of cable connection interfaces
Smart Grid and Automation
Encapsulated 3 current transformers(±0.2%)
Encapsulated 6 voltages sensors maximum(±5%)
Product Dimensions
Type Test
SOJO Electric SVR automatic recloser has passed the complete type tests in accordance with relevant IEC and IEEE standards and has been granted KEMA certificates.
SJFD2000 Microprocessor Controller
SJFD2000 multifunctional devices offer a comprehensive solution for protecting and controlling distribution feeders or reclosers. Optionally they can provide loop automation. Besides the main protection functions, they include monitoring and operation features as well as logic programming, and events and fault reporting providing comprehensive switchgear (circuit breaker, recloser or LBS) management local and remote capabilities.
SJFD2000 is a cost-effective solution for protection and control systems for which IEC 61850 standard compliance is required, including access in other protocols and web services as well.
Item | Unit | Data | |||
---|---|---|---|---|---|
15.5kV | 27kV | 38kV | |||
Rated Voltage |
kV |
15.5 |
27 |
38 |
|
Rated Frequency |
Hz |
50/60 |
50/60 |
50/60 |
|
Rated Current |
A |
630/800 |
630/800 |
630/800 |
|
Rated Short Circuit Breaking Current |
kA |
16 |
12.5/16 |
12.5 |
|
Rated Peak Withstand Current |
kA |
41.5/32.5 |
41.5/32.5 |
32.5 |
|
Rated Short Time Withstand Current IDuration |
kA/s |
16/3 |
12.5/3 16/3 |
12.5/3 |
|
Rated Short-circuit Making Current (peak) |
kA |
32.5/41.5 |
32.5/41.5 |
32.5 |
|
Rated cable-charging current switching |
A |
10 |
25 |
40 |
|
Rated line-charging current switching |
A |
2 |
5 |
5 |
|
Mechanism Duration |
Ops |
10000 |
|||
1 min Power Frequency Withstand Voltage |
DRY |
kV |
50 |
60/70 |
70 ( 80) 1 |
Rated lightning impulse withstand voltage (BIL) |
kV |
125 |
125/150 |
170 ( 200) 1 |
|
Rated operating sequence |
|
O-0.2s-CO-2s-CO-2s-CO |
|||
Number of max. tripping operations |
n |
4 |
|||
Actuator type |
|
Magnetic1 |
|||
Standards |
|
IEC62271-111 - 2019 IEEE C37-60 |
|||
Pollution level as defined in IEC 60815 |
|
IV - Very Heavy |
|||
Protection degree |
|
IP67 |
|||
Ambient air temperature range |
℃ |
-40 to +55 |
|||
Current sensing technology per phase |
|
current transformer |
|||
Voltage sensing technology per phase |
|
voltage sensor |
|||
Controller(IED) |
|
SJFD2000 (also compatible with other brands) |
|||
Weight |
kg |
90 |
130 |